USE “SEARCH” TAB ON the top right side FOR ALL INSTRUMENTATION RELATED TOPICS
Cable: 1pair x 1.5 mm2 FRLS 11.9 OD 7.3 ID-Gland: 0.5″NPTM Range 10 to 14
-
Cable: 1pair x 1.5 mm2 FS 13.1 OD 8.5 ID-Gland: 0.5″NPTM Range 14 to 18
-
Cable: 2C x 1.5 mm2 FRLS 11.6 OD 7.3 ID-Gland: 0.5″NPTM Range 10 to 14
-
Cable: 2C x 1.5 mm2 FS 12.8 OD 8.2 ID-Gland: 0.5″NPTM Range 14 to 18
-
Cable: 2C x 2.5 mm2 FRLS 12.4 OD 7.8 ID-Gland: 0.5″NPTM Range 10 to 14
-
Cable: 2C x 2.5 mm2 FS 13.6OD 9.0 ID-Gland: 0.5″NPTM Range 14 to 18
-
Cable: 1T x 1.5 mm2 FRLS 12.3 OD 7.7 ID-Gland: 0.5″NPTM Range 10 to 14
-
Cable: 1P x 1.5 mm2 FRLS 11.9 OD 7.3 ID-Gland: 0.75″ETM Range 10 to 14
-
Cable: 1Px 1.5 mm2 FS 13.1 OD 8.5 ID-Gland: 0.75″ETM Range 14 to 18
-
Cable: 2Cx 1.5 mm2 FRLS 11.6 OD 7.3 ID-Gland: 0.75″ETM Range 10 to 14
-
Cable: 2Cx 1.5 mm2 FS 12.8 OD 8.2 ID-Gland: 0.75″ETM Range 14 to 18
-
Cable: 2Cx 2.5 mm2 FRLS 12.4 OD 7.8 ID-Gland: 0.75″ETM Range 10 to 14
-
Cable: 2Cx 2.5 mm2 FS 13.6 OD 9.0 ID-Gland: 0.75″ETM Range 14 to 18
-
Cable: 1Tx 1.5 mm2 FRLS 13.6 OD 9.0 ID-Gland: 0.75″ETM Range 10 to 14
-
Cable: 10Cx 1.5 mm2 FRLS 18.4 OD 13.1 ID-Gland: 1″ETM Range 18 to 21
-
Cable: 10Cx 1.5 mm2 FS 22.1 OD 15.7 ID-Gland: 1″ETM Range 21 to 24
-
Cable: 10Cx 2.5 mm2 FRLS 19.9 OD 14.6 ID-Gland: 1″ETM Range 21 to 24
-
Cable: 10Px 0.75 mm2 FRLS 23.6 OD 16.8 ID-Gland: 1″ETM Range 24 to 27
-
Cable: 10Px 0.75 mm2 FS 27.9 OD 21.5 ID-Gland: 1.5″ETM Range 30 to 34
-
Cable: 10Tx 0.75 mm2 FRLS 26.6 OD 19.8 ID-Gland: 1.25″ETM Range 27 to 30
-
Cable: 10Tx 1.5 mm2 FRLS 31.3 OD 24.5 ID-Gland: 1.5″ETM Range 30 to 34
-
Cable: 10Tx 1.5 mm2 FS 36.2 OD 29.4 ID-Gland: 2″ETM Range 30 to 37
-
Cable: 20Cx 1.5 mm2 FRLS 21.7 OD 16.2 ID-Gland: 1″ETM Range 21 to 24
-
Cable: 20Cx 1.5 mm2 FS 25.5 OD 19.3 ID-Gland: 1.25″ETM Range 27 to 30
-
Cable: 20Cx 2.5 mm2 FRLS 24.5 OD 18.3 ID-Gland: 1.25″ETM Range 24 to 27
-
Cable: 20Cx 2.5 mm2 FS 27.6 OD 21.4 ID-Gland: 1.25″ETM Range 27to 30
-
Cable: 20Px 0.75 mm2 FRLS 31.1 OD 24.3 ID-Gland: 1.25″ETM Range 30 to 34
-
Cable: 20Px 0.75 mm2 FS 35.6 OD 28.8 ID-Gland: 2″ETM Range 41 to 46
-
Cable: 20Tx 1.5 mm2 FS 52.6 OD 42.2 ID-Gland: 2.5″ETM Range 53 to 61
-
Cable: 40Cx 1.5 mm2 FRLS 28.4 OD 22.0 ID-Gland: 1.25″ETM Range 27 to 30
Cable: 40Cx 1.5 mm2 FS 32.8 OD 26.4 ID-Gland: 1.5″ETM Range 30 to 37
-
Cable: 40Cx 2.5 mm2 FRLS 31.9 OD 25.3 ID-Gland: 1.5″ETM Range 30 to 34
-
Cable: 40Cx 2.5 mm2 FS 35.7 OD 29.3 ID-Gland: 2″ETM Range 37 to 41
-
Cable: 5Px 0.75 mm2 FRLS 18.0 OD 12.7 ID-Gland: 1″ETM Range 18 to 21
-
Cable: 5Px 0.75 mm2 FS 21.8 OD 15.4 ID-Gland: 1″ETM Range 21 to 24
-
Cable: 5Tx 1.5 mm2 FRLS 24.5 OD 18.1 ID-Gland: 1.25″ETM Range 24 to 27
-
Cable: 5Tx 1.5 mm2 FS 28.3 OD 21.5 ID-Gland: 1.25″ETM Range 27 to 30
-
Cable: 1Px 1.5 mm2 FRLS 11.9 OD 7.3 ID-Gland: 1″NPT Range 10 to 14
-
Cable: K TYPE THERMOCOUPLE COMP 12.5 OD 7.9 ID-Gland: 0.75″ETM Range 10 to 14
All Cable OD & ID can have + or – 2 in sizes tolerance and cable glands should be stainless steel ,double compression for out door hazardous area ,stainless steel with nickel platingwith neoprene seal neoprene bushing,IP-66 for steel wire armoured cable,complete with locknut,earth tagPVC shroud and nylon entry threads/seal for IP66 ingress protection
Tolerance is about (+/-)3 %
Pingback: My Posts till now | Kishore Karuppaswamy
Pingback: All my posts till now | Kishore Karuppaswamy
Pingback: Instrumentation related to a motor driven pump | Kishore Karuppaswamy
Pingback: Calibration of Temperature transmitter zero trimming | Kishore Karuppaswamy
Pingback: Painting Procedure | Kishore Karuppaswamy
Pingback: Instrumentation Cable design specification | Kishore Karuppaswamy
Pingback: Acceptable accuracy ranges of Instruments | Kishore Karuppaswamy
Pingback: Standard Power supply requirements for Instrumentation devices | Kishore Karuppaswamy
Pingback: General design requirements of Instrumentation part 2 | Kishore Karuppaswamy
Pingback: AK ENCON ENGINEERING SERVICES | Kishore Karuppaswamy
Pingback: Bastard Esterraj Stephen and MC GSN Raju | Kishore Karuppaswamy
Pingback: Boiler | Kishore Karuppaswamy
Pingback: General design requirements of Instrumentation part 5 | Kishore Karuppaswamy
Pingback: All my posts till now | kishore koduvayur
Pingback: AS-i (Actuator sensor-Interface Protocol) | Kishore Karuppaswamy
Pingback: Flow transmitter DP type | Kishore Karuppaswamy
Pingback: Profibus | Kishore Karuppaswamy
Pingback: Calibration of siemens sipart PS2 | Kishore Karuppaswamy
Pingback: Instrumentation engineering | Kishore Karuppaswamy